Detektor Kebakaran

NITTAN EVA DPH
DETEKTOR KEBAKARAN 

detektor kebakaranEVA DPH adalah detektor kebakaran kombinasi photoelectric dan  heat detector. Dilengkapi screen stainless steel yang berfungsi mencegah masuknya serangga kecil dan kontaminan udara – salah satu penyebab munculnya false alarm.

EVA DPH bisa diintegrasikan dengan Nittan fire alarm control panel NFU 7000. Detektor ini akan menginformasikan alamat dimana detector ini terpasang. Detektor ini dilengkapi 2 lampu indicator : Hijau dan Merah. Indikator lampu hijau menginformasikan bahwa EVA DPH bekerja sesui fungsinya. Lampu indicator merah menginformasikan adanya alarm.

Detektor kebakaran EVA DPH, bekerja dalam range tegangan 20 VDC – 30 VDC, smoke sensitivity xx %/Ft to xx %/Ft dan alarm temperature 57°C (134°F), mampu menampung 254 address per loop.

Detektor EVA DPH bisa digunakan di commercial buiding, hotel, villa, pabrik.

Nittan Spera NFU 7000

NITTAN SPERA NFU 7000
system configuration

nittan spera nfu 7000

FEATURES NITTAN SPERA NFU 700 :

  • One driver card capable of 2 loops is equipped as standard
  • NITTAN SPERA NFU-7000 has 3 capability of driver card storage (max 6 loops), NFU-7000-L has 7 capability (max 14 loops)
  • One loop supports 254 addresses which can be wired in Class A (Style 6 or 7) or Class B (Style 4)
  • Use of shielded cable is not required for SLC loops
  • Modular design
  • Four Class A/B (Style Z/Y) Notification Appliance Circuits rated at 1.7 Amps each
  • One Auxiliary power supply, rated 1.7 Amps at 24VDC in addition to one resettable 4-wire power supply
  • Large 16 line x 40 character Back-lit LCD Display with user friendly menu
  • Correlatable Switch Inputs which allow for multifunctional outputs
  • Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor
  • Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble
  • RS-232 port for remote system printer
  • Two Event History Logs comprised of a 1000 event alarm history log for alarm related events and a 5000 event log for all events
  • Supports three configuration files (current, previous and next configuration) with “hot swap” support
  • Supports Conventional Hardwire Adder Modules
  • Built-in One Man Walk Test operation
  • Provides drift compensation for Photoelectric Smoke Detectors
  • Capability to adjust Intelligent Smoke Detector sensitivity levels
  • Real time 3D graphical monitoring and control using Nittan’s NFU-Graphic-monitor
  • BACnet support
  • Supports Boolean logic functions
  • Built-in Ethernet port
  • UL listed for Smoke Control
  • Manual Control Function
  • Input Simulation Function
  • Multiple group bypass function with built-in false alarm prevention technology
    • Network Node Bypass
    • Node Outputs Bypass
    • Input Zone Bypass
    • Relay Disconnect
    • Device/Circuit Bypass

Network Features

  • Up to 63 panels
  • Peer-to-peer network communications
  • Mutual surveillance / 2 way control available
  • Class A (Style 6 or 7) or Class B (Style 4) wiring configuration
  • Arcnet Network Communications protocol